product info

Differential Pressure & Communication Type Digital Pressure Switch SP-16 Series

The SAME TECHNOLOGY SP-16 Series is a high-precision differential pressure digital switch featuring a 5-digit 7-segment display with up to 1 Pa resolution and ±0.2% F.S. repeatability for micro-range pneumatic control. Equipped with RS485 MODBUS communication alongside a retained 1-channel switch output (NPN/PNP), it is engineered for air filter clogging monitoring, pipeline leakage detection, and automated industrial equipment

  • Product Series :

    SP-16: Differential Pressure Communication Type
  • Signal Output Type :

    030: 1-channel NPN + 1 set of RS485 communication | 031: 1-channel PNP + 1 set of RS485 communication
  • Air Pressure fitting Type :

    MM: Dual air nozzle fitting female M5 thread
  • Air Pressure Input Range :

    CA:-500~500.0Pa | CC:-2.000~2.000kPa(Not available temporarily) | CD:-5.000~5.000kPa | CE:-10.000~10.000kPa | CF:-40.000kPa~40.000kPa | CG:-100.00kPa~100.00kPa | CB:-1000.0~1000.0Pa

Product Overview

The SAME TECHNOLOGY SP-16 Series Differential Pressure & Communication Type Digital Pressure Switch is engineered for accurate micro-pressure monitoring and networked industrial automation. Combining a clear dual-color 5-digit 7-segment LED display (max. 1 Pa resolution) with ±0.2% F.S. repeatability and ±2% F.S. display accuracy, the SP-16 delivers stable small-range differential pressure control. It integrates an RS485 MODBUS communication interface while retaining 1-channel switch output (NPN or PNP), making it well suited for air filter clogging monitoring, pipeline leakage testing, and space-saving multi-unit panel installations.

Product Highlights

5-Digit Display & 1 Pa Resolution

Dual-color 5-digit 7-segment display provides up to 1 Pa maximum resolution and ±2% F.S. display accuracy for clear real-time pressure reading.

±0.2% F.S. Repeatability

High repeatability ensures consistent switching thresholds and dependable control in low-pressure and micro-differential pneumatic lines.

MODBUS RS485 + 1-Ch Switch

Supports industrial RS485 MODBUS communication for PLC/SCADA data acquisition while retaining 1 independent NPN or PNP switch output.

SP-16 Series Differential Pressure Digital Pressure Switch

Selection Method & Model Specifications

Model Code Example: SP - 16 - CC - 030 - MM (① Product Series – ② Air Pressure Input Range – ③ Signal Output Type – ④ Air Pressure Fitting Type)

Code Item Specification / Options
① Product Series 16: Differential Pressure Communication Type
② Air Pressure Input Range CA: -500~500.0Pa   |   CB: -1000.0~1000.0Pa   |   CC: -2.000~2.000kPa (Not available temporarily)
CD: -5.000~5.000kPa   |   CE: -10.000~10.000kPa
CF: -40.000kPa~40.000kPa   |   CG: -100.00kPa~100.00kPa
③ Signal Output Type 030: 1-channel NPN + 1 set of RS485 communication
031: 1-channel PNP + 1 set of RS485 communication
④ Air Pressure Fitting Type MM: Dual air nozzle fitting, female M5 thread

Typical Industrial Applications

  • • Air Filter Clogging Detection: Connects the high-pressure and low-pressure channels across a compressed air filter to monitor pressure drop and trigger timely filter replacement alerts.
  • • Pipeline Leakage Detection: Compares the test object against a reference standard via solenoid valves to detect minute differential pressure changes caused by air leaks.
  • • Pipeline Filter Air Monitoring: Continuously tracks differential pressure across duct and pipeline filter elements to maintain stable airflow and equipment efficiency.
SP-16 Air Filter Clogging and Leakage Detection Diagram
SP-16 Pipeline Filter Air Monitoring and 1 Pa Resolution Display

Circuit Wiring & Pin Definitions

The SP-16 Series operates on a DC 12–24V power supply and is available in two output configurations: SP-16□030□ (1-channel NPN + 1 set of RS485) and SP-16□031□ (1-channel PNP + 1 set of RS485). Refer to the 5-pin cable definition below:

Pin No Wire Color Signal Name Function Definition
1 Brown DC+ Positive Power Supply (DC 12–24V)
2 Black OUT1 Switch Output 1 (NPN for 030 / PNP for 031)
3 White 485A RS485 Communication A (MODBUS)
4 Orange 485B RS485 Communication B (MODBUS)
5 Blue DC− Negative Power Supply (0V)
Wiring Precaution: For communication-type wiring, always connect the RS485 communication cables (485A / 485B) first, then connect the DC power cables (DC+ / DC−) to prevent short circuits and potential product damage.
SP-16 Circuit Wiring Diagram NPN PNP RS485 MODBUS

Mounting Methods & Optional Accessories

Accessory Models (Optional, Separate Order Required):

  • 1. L-type metal mounting bracket: XP-BT-04
  • 2. Z-type metal mounting bracket: XP-BT-05
  • 3. Panel mounting bracket: XP-PA-01
  • 4. Barbed fitting, internal M5 fitting for φ4 air tube: XP-BT4-M5
  • 5. Barbed fitting, internal M5 fitting for φ6 air tube: XP-BT6-M5
  • 6. Quick screw fitting, internal M5 fitting for φ4 air tube: XP-KN4-M5
  • 7. Quick screw fitting, internal M5 fitting for φ6 air tube: XP-KN6-M5
  • • Compact Panel Mounting & Protective Cover: Supports tight side-by-side or vertical multi-unit panel arrays to save cabinet space, with an optional snap-on front protective cover to prevent accidental button operation.
SP-16 Mounting Brackets XP-BT-04 XP-BT-05 and Protective Cover

Frequently Asked Questions (FAQ)

Q: What is the difference between SP-16 030 and SP-16 031 models?

A: Both models include 1 set of RS485 MODBUS communication and operate on DC 12–24V. The difference lies in the retained switch output channel (OUT1): SP-16 030 provides a 1-channel NPN output, while SP-16 031 provides a 1-channel PNP output.

Q: What resolution and repeatability can the SP-16 Series achieve?

A: The SP-16 Series features a 5-digit 7-segment LED display with a maximum resolution of 1 Pa, display accuracy of ±2% F.S., and repeatability of ±0.2% F.S., making it suitable for precise small-range differential pressure monitoring.

Q: What wiring sequence should be followed when connecting RS485 communication?

A: Always connect the communication wires (White 485A and Orange 485B) first before connecting the DC 12–24V power wires (Brown DC+ and Blue DC−) to avoid short circuits and damage to the internal communication circuit.

Q: Are the XP-BT-04 and XP-BT-05 mounting brackets included with the switch?

A: No, both the L-type metal mounting bracket (XP-BT-04) and the Z-type metal mounting bracket (XP-BT-05) are optional accessories and must be ordered separately based on your installation layout.

Company Advantages & Factory Strength

  Factory Facility Production Line Quality Control
Company Certifications Company Awards Global Delivery
Leave A Message
If you are interested in our products and want to know more details,please leave a message here,we will reply you as soon as we can.
Leave A Message
If you are interested in our products and want to know more details,please leave a message here,we will reply you as soon as we can.